Project Description

AIR VENT “ROMA” TYPE

AIR VENT "ROMA" TYPE

AVAILABLE MODELS
606
: With plug cock
606SRM: Without plug cock

TECHNICAL FEATURES

Pressure:
Maximum working pressure (PN)16 bar
Minimum accumulation 0.5 bar (Grade A according to EN 12266-1)
Range of operation air evacuation from 0,5 bar to 16 bar (tolerance ± 10% max. detected)
Temperature:
Maximum working temperature (TS) 0°C (excluding ice) + 60°C
Minimum plant storage -20°C (with recess fluid discharged)
Threading:
Pipeline connection threads according to ISO 228/1
Requirements and tests as per:
Air vents EN 1074-4
Seat tightness EN 1074-4 §5.2.2
Pressure resistance EN 1074-4 §5.1.1
Pressure resistance EN 1074 – 4 §5.1.1

DISPOSAL
Prior to disposal, disassemble the valve and separate the component according to various materials. Please refer to product literature for more information. Forward sorted material to recycling (e.g. metallic materials) or dispose it, according to local and currently valid legislation taking into consideration the environment.

GENERAL INFORMATION
Performance data, including pressure – temperature ratings have been developed from published standards, supplier material certifications, design calculations and in-house testing. They cover typical applications and are provided as a general guideline.